LINE VOLTAGE, FREQUENCY & ATTITUDE CHANGE
CORD AND PLUG CONNECTED EQUIPMENT

COUNTRY
LINE TO GROUND
LINE TO LINE
FREQUENCY
VOLTAGE RANGE
SINGLE PHASE
VOLTAGE ...CURRENT MAX
SINGLE PHASE
VOLTAGE ...CURRENT MAX
AUSTRALIA 240V 415V / 240V 50HZ +6% 240V 20-25A
(NOTE 2)
415V
240V
125A
(NOTE 1)
AUSTRIA 220V
(NOTE 4)
380V (NOTE 4) 50HZ +5% 220V (NOTE 6) 380V 125A
(NOTE 1)
BELGIUM 220V
(NOTE 4) or 127V
(NOTE 5)
380V or
220V(NOTE 4)
50HZ +5% 127V
220V
16A / 63A
(NOTE 9)
220V
380V
125A
(NOTE 1)
BRAZIL 127V or
220V
220V or
380V
60HZ (NOTE 6) 220V
127V
16A- / 63A
(NOTE 9)
380V
220V
125A
(NOTE 1)
CANADA 127V or
374V
208V / 220V
480V / 600V
60HZ +4%
-8.3%
120V
240V
16A / 30A 208V / 240V
480V / 600V
200A
DENMARK 220V
(NOTE 4)
380V (NOTE 4) 50HZ +10% 220V 16A / 30A
(NOTE 9)
380V 125A
(NOTE 1)
FINLAND 220V or
240V
(NOTE 4)
380V or 415V 50HZ +10% 220V
240V
16A / 63A
(NOTE 9)
380V 125A
(NOTE 1)
FRANCE 220V
(NOTE 4)
380V (NOTE 4) 50HZ (NOTE 6) 220V 16A / 63A
(NOTE 9)
380V 125A
(NOTE 1)
WEST GERMANY 220V
(NOTE 4)
380V (NOTE 4) 50HZ +10% 230V 16A / 63A
(NOTE 9)
400V 125A
(NOTE 1)
HONG KONG 220V
(NOTE 4)
346V (NOTE 4) 50HZ +6% 200V 60A 346V 125A
(NOTE 1)
ITALY 220V
(NOTE 4)
380V (NOTE 4) 50HZ +10% 220V 16A / 63A
(NOTE 9)
380V 125A
(NOTE 1)
JAPAN
EAST

WEST
100v or 200V
(NOTE 8)
415V
50HZ

60HZ
+10% 100V 15A 415V 125A
(NOTE 1)
NETHERLANDS 220V (NOTE 4) 380V (NOTE 4) 50HZ +10% 220V 16A / 63A
(NOTE 9)
380V 125A
(NOTE 1)
NORWAY 230V 400V 50HZ +10% 230V 16A / 63A
(NOTE 9)
400V 125A
(NOTE 1)
SPAIN 220V 380V (NOTE 4) 50HZ +10% 230V 16A / 63A
(NOTE 9)
400V 125A
(NOTE 1)
SWEDEN 220V (NOTE 4) 380V (NOTE 4) 50HZ +6% -10%  220V 16A / 63A
(NOTE 9)
  
380V 125A
(NOTE 1)
SWITZERLAND 220V 380V 50HZ +10% 220V 16A / 63A
(NOTE 9)
380V 125A
(NOTE 1)
UNITED KINGDOM 240V (NOTE 4) 415V 50HZ (NOTE 6) 240V 13A / 63A
(NOTE 9)
415V 125A
(NOTE 1)
U.S.A. 120V /265V 208V / 240V / 460V 60HZ +10% 120V / 240V 50A 208V / 240V
460V
60A

NOTE 1:
THIS VALUE IS GIVEN FROM THE HIGHEST KNOWN PLUG CURRENT RATING CURRENTLY AVAILABLE ON THE MARKET; IEC 309 ALLOWS A CURRENT UP TO 200A, BUT LIMITS THE DISCONNECTING FORCE. THIS DISCONNECTING FORCE LEVEL ALLOWS ONLY CONNECTION SYSTEMS UP TO 125A TO BE BUILT.

NOTE 2:
THIS VALUE IS DETERMINED BY THE HIGHEST SPECIFIED CURRENT THROUGH THE NEUTRAL.

NOTE 3:
THE MAXIMUM DRAWABLE CURRENT VALUE MIGHT BE EXCEEDED WITH SPECIAL PERMISSION FROM THE LOCAL POWER SUPPLY COMPANY.

NOTE 4:
ALL EUROPEAN COUNTRIES AND HONG KONG AGREED TO CHANGE THE NOMINAL VOLTAGE TO A COMMON LEVEL OF 230/400V 50HZ BY 1992.

NOTE 5:
THE 127/220V SYSTEM IS THE OLD STANDARD AND IS FOUND VERY SELDOM, COMMMERCIAL BUILDINGS ARE ALL FURNISHED WITH 220/380V. THE STANDARD VOLTAGE FROM 1992 ON IS 230/400V 50HZ.

NOTE 6:
INFORMATION NOT AVAILABLE

NOTE 7:
MUST BE AGREED WITH THE SUPPLY COMPANY

 

Call us toll-free today at 800.818.4916 to or work online to request a quote for your electric power cords.